GP800(1~15KVA)
1:1 Phase
-
Application
-
Features
-
Specifications
Application:
Critical servers, storage application and other
networking equipment.
� True on-line double conversion design providing all
power protection
� Sine wave pulse width modulation.
� IGBT inverter design
� Wide Input voltage windows
� Pure sine wave output with less than 3% THD
� Expandable backup time
� Generator compatible
� Cold start
� Load/Battery power meter display
� Overload, on-line, battery status LED/LCD
� Advanced Battery Management
� Automatic charging in UPS off mode
� Zero transfer time on AC mode to/ from battery mode,
AC mode to/ from bypass mode
� Smart RS-232 communication port
� Optional SNMP card
Model |
|
GP801 |
GP802 |
GP803 |
GP804 |
GP806 |
GP808 |
GP810 |
GP812 |
GP815 |
Capacity |
|
1KVA |
2KVA |
3KVA |
4KVA |
6KVA |
8KVA |
10KVA |
12KVA |
15KVA |
Input |
Voltage Range |
170-270VAC or 85-135VAC
|
Frequency |
50/60Hz 5% |
Phase |
Single phase + GND |
Max input current (110V) |
12A |
24A |
36A |
48A |
72A |
96A |
120A |
144A |
180A |
Max input current (220V) |
6A |
12A |
18A |
24A |
36A |
48A |
60A |
72A |
90A |
Output |
Voltage Range |
220VAC 1% or 110VAC 1%
|
Frequency |
50/60Hz 0.5% |
Phase |
Single phase + GND |
THD |
<3%(linear load) |
Power Factor |
0.8 |
Short Circuit Protection |
Current limit, turn off
automatically, Switch protect |
Overload Capacity |
Overload 110%-150% ,
20s later go to bypass, |
|
|
automatically resume
when load become normal |
Battery |
Type |
Sealed lead acid,
maintenance free |
DC |
48VDC(192V Optional) |
192VDC |
Charge current |
4.2A |
4.2A |
4.2A |
4.2A |
4.2A |
4.2A |
4.2A |
4.2A |
4.2A |
Charge Time |
90% capacity after 8
hours |
Panel
indication |
LCD |
Working mode, I/P and
O/P voltage, I/P and O/P frequency,
Battery voltage, load percentage, UPS
inner temperature |
LED |
low battery, online,
inverter, bypass, abnormal |
Efficiency |
Whole unit |
>0.85 |
Communication |
1.Power status 2.UPS
shutdown 3.monitor UPS status |
|
4.UPS self test
5.auto-save files |
Protection |
Surge Protection |
IEEE527B |
Noise |
FCC.A |
Audible Noise |
<55db at 1 meter |
Environment |
Temperature |
0~40 |
Humidity |
0%-95% |
General |
Net/Gross weight
(without battery) kg |
46/61 |
63/78 |
75/90 |
65/85 |
69/89 |
105/135 |
115/145 |
125/155 |
262/302 |
Unit Dimension (W x D x
H)mm |
230x670x538 |
230x635x700 |
305x650x867 |
725x430x1180 |
Packing Dimension (W x D
x H)mm |
410x780x770 |
410x810x950 |
550x853x1090 |
1010x740x1510 |
|
|
|
|