HP900C/HP900C-RM(6~10KVA) 1:1 Phase

  • Application
  • Features
  • Specifications

 

Application:
Rack mounted server and other networking equipment.

 

 

Features:

High frequency and double conversion on-line technology
Fully digitized microprocessor control
Wide input voltage range
LCD display
Cold start
Parallel capacity
7. Advanced battery management
Automatic battery charge in UPS off mode
Lightning and surge protection
Short circuit and overload protection
Fan speed auto control when loads varies
Optional extension battery pack
EMI/RFI noise filter
Smart RS232 communication with monitoring software
Optional SNMP Card slot

Model HP960C HP960C-RM HP9100C HP9100C-RM
Capacity 6KVA/4.2KW 10KVA/7KW
Input Voltage Range 176±5VAC~276±5VAC
Frequency Range 46~54Hz±0.5Hz or  
56~64Hz±0.5Hz auto sensing
Phase Single phase
Power Factor ≥ 0.98
Output Voltage Range 220Vac±1%
Phase Single phase
Frequency Range 50Hz/60Hz±0.2%(battery mode)
THD (linear load) <2%
THD (non-linear load) < 6%
Overload Capability 105%~130%, 10min turn to bypass mode;>130% 1s turn to bypass mode
Crest Factor 3:1(max)
Short Circuit Protection 5 cycles turn off inverter, no transfer to bypass, provide alarm (AC mode)
5 cycles turn off inverter, provide alarm (battery mode)
input fuse blown or breaker action (bypass mode)
Waveform pure sine wave
Transfer Time Between AC Mode and Battery Mode 0ms
Transfer Time Between AC Mode and Bypass Mode 0ms
Efficiency ≥ 88%
Battery Model 12V sealed lead acid maintenance free
DC Voltage 240VDC
Configuration 20×12V/7AH
Backup Time ( half load) 20min N/A 13min N/A
Backup Time (full load ) 7min N/A 5min N/A
Charge Current(standard unit) 1A  
Charge Current(long time unit) 5A
Recharge Time 90% capacity after 8 hrs charging
Communication Interface RS232 ; SNMP (optional)
Parallel port Parallel availability for redundancy and load sharing up to three units
LCD Indication 1, Input voltage/frequency, battery voltage, output voltage/frequency, load watt/VA value and percent, inverter temperature
2, Operation mode such as “on line”, “on batt”, or “or bypass”
LED Indication 1, Green LED for normal operation,
2, Yellow LED for warning condition
3, Red LED for abnormal operation
Noise Level <55dB
Environment Temperature 0~40
Humidity 0%~95% (non-condensing)
Altitude <1500m
Storage Temperature 0~40 
Other Standard Unit Net/Gross Weight 89/104kg N/A 92/107kg N/A
Long Time Unit Net/Gross Weight 33/43Kg 22/25Kg 36/46Kg 22/25Kg
Dimension (W×D×H)mm   270×570×720 440×656×176 270×570×720 440×656×176